THE UTILIZATION/IMPLEMENTATION OF A UNIFIED POWER FLOW CONTROLLER (UPFC) TO ENHANCE VOLTAGE STABILITY WITHIN A HEAVILY CONGESTED ELECTRICAL NETWORK
Abstract
THE UTILIZATION/IMPLEMENTATION OF A UNIFIED
POWER FLOW CONTROLLER (UPFC) TO ENHANCE
VOLTAGE STABILITY WITHIN A HEAVILY
CONGESTED ELECTRICAL NETWORK
BY
NNA MICHAEL CHIBUIKEM
FUO/18/EEE/7613
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
ENGINEERING,
FACULTY OF ENGINEERING, FEDERAL UNIVERSITY
OTUOKE, NIGERIA
A PROJECT SUBMITTED TO THE DEPARTMENT OF
ELECTRICAL AND ELECTRONICS ENGINEERING,
FACULTY OF ENGINEERING, FEDERAL UNIVERSITY
OTUOKE
IN PARTIAL FULFILMENT OF THE REQUIREMENT
FOR THE AWARD OF BACHELOR OF ENGINEERING
(B.Eng.) DEGREE IN ELECTRICAL AND
ELECTRONICS ENGINEERING
AUGUST, 2024.
DECLARATION
I declare that this research work entitled ‘THE
UTILIZATION/IMPLEMENTATION OF A UNIFIED
POWER FLOW CONTROLLER (UPFC) TO ENHANCE
VOLTAGE STABILITY WITHIN A HEAVILY
CONGESTED ELECTRICAL NETWORK” was carried out
by me in the Department of Electrical and Electronics
Engineering. All sources of information used in this work have
been properly acknowledged both in the text and in the list of
references. This project has not been earlier submitted for the
award of another degree in this or any other institution.
NNA MICHAEL CHIBUIKEM
_________________ _______________
(FUO/18/EEE/7613)
SIGNATURE DATE
CERTIFICATION
This is to certify that this research work on ‘THE
UTILIZATION/IMPLEMENTATION OF A UNIFIED
POWER FLOW CONTROLLER (UPFC) TO ENHANCE
VOLTAGE STABILITY WITHIN A HEAVILY
CONGESTED ELECTRICAL NETWORK”, was
independently carried out by NNA MICHAEL CHIBUIKEM
with Matriculation Number, FUO/18/EEE/7613, meets the
regulation governing the award of Bachelor of Engineering
(B.Eng.) degree in Electrical and Electronics Engineering of
Federal University Otuoke, Nigeria during the 2023/2024
academic session, it is approved due to its contribution to
knowledge.
………………………
………………………
PROF. DONATUS BASSEY
DATE
SUPERVISOR
…………………………………
………………………
ENGR. PROF. EMERITUS ADEKOLA
SULAIMON DATE
HEAD OF DEPARTMENT
………………………………
…………………………
ENGR. PROF. SCOTT BERNARD AKPILA
DATE
DEAN, FACULTY OF ENGINEERING
…………………………… ……………………………
..………………………..
EXTERNAL EXAMINER
SIGNATURE DATE
DEDICATION
This research work is dedicated to the ALMIGHTY GOD IN
HEAVEN, for His infinite Mercy and Grace, and for giving me
spiritual and moral support to complete this work
AKNOWLEDEMENTS
First of all, I am grateful to God for His protection, provision
and guidance upon my life and His unconditional Love towards
me which has brought about the successful completion of this
program.
With a grateful heart filled with appreciations, I acknowledge
the contribution of my lovely mother, Mrs. Nna Christiana
Omasirichi, my ever young and caring grandmother, Mother
Nna Ada and entire family for their time, support and
understanding and mostly their prayers for me all through my
B.Eng. program.
Special appreciation to the amiable Head of Department of the
prestigious Electrical Electronics Engineering, Engr. Prof.
Emeritus Adekola Sulaimon for your continuous care and
support. To my supervisor, Prof. Donatus Bassey Emmanuel,
thank you for the privilege to be under your care and guidiance.
I must also express my gratitude to Engr. Adebayo Adeniyi, to
whom stood as a father to me to ensure the success of this
project, and also for ensuring that everything went well with the
academic activities of the students in the department and for his
readiness to assist and advice.
Also, I express my appreciation to all the staff of Electrical and
Electronic Engineering, Federal University Otuoke for their
good works. I want to also appreciate the entire NUESA and
SEEES for giving me the privilege to serve. Members of the
National Union of Rivers State Students FUO Chapter, the entire
family of Salvation Ministries Home of Success Otuoke Satellite
and Campus Ministry thank you for a wonderful experience.
I am also thankful to my entire course mates, you all are
wonderful, and to my friends; Dappa Prince, Pascal,
Tamunogbarachua George, Chidi Joy, Roy, Osomu Hope, Ekeh
Jane, Queen Favour, Agbo John, Levi Nnamani and colleagues
worthy of mention in no particular order,
Finally, I would like to thank my humble self. for making the
most of the chances given to me to study with and from such
brilliant minds.
ABSTRACT
The daily increase in electricity useage puts strain on the electric
networks of the power grids, causing congestion and unstable
voltage which may lead to grid collapse. As a result, maintaining
voltage stability throughout the network becomes extremely
difficult. In order to prevent such, creating system redundancy is
essential to guarantee voltage and system stability, but this has
constraints on both an economic and environmental level. In
order to ensure a dependable system, a more economical cost
effective approach is presented that makes use of already-
existing network components and incorporates less expensive
schemes and rules. To improve overall system performance,
including voltage profile across the network buses, transmission
line flows, and losses, Flexible Alternating Current
Transmission System (FACTS) such as the Unified Power Flow
Controller (UPFC) must be used. One of the FACTS
components that can offer phase angle shifting, line impedance
control, and VAR correction is the Unified Power Flow
Controller (UPFC). This research introduces the UPFC as an
effective FACTS device to improve the overall performance of
an electric system (grid) for effective functioning and voltage
output.
KEYWORDS
FACTS Devices, Unified Power Flow Controller (UPFC),
Voltage Stability, Power Flow Improvement.
TABLE OF CONTENT
Title
Page………………………………………………………………
….……………………I
Declaration..…………………………..…………………………
…………………………......II
Certification……………………………………………………
……………………………...III
Dedication………….……………………………………………
…………………………....IV
Acknowledgements.…………...…………………………………
………………………..…..V
Abstract………….………………………………………………
……………………….......VI
Table of
Content…..………………………………………………………
……………..….VII
List of
Figures……………………………………………………………
……………...……IX
List of
Tables……………………………………………………………
…………...…..……X
CHAPTER ONE: INTRODUCTION
1.1 Background of the
Study.………………………………………………………….....
1
1.2 Statement of
Problem…...………………………………………..……………
……..2
1.3 Justification of the
Study……………………………………………………………..
3
1.4
Aim……………………………………………………...………
……………………3
1.5
Objectives…………….…………………………………….……
…………………...3
1.6 Scope of
Study…………….……………………………….………………
…………3
1.7
Limitations……………………………………...…...………..…
…………………....3
1.8 Thesis
Organization………………………...…………………………..
……….........4
CHAPTER TWO: LITERATURE REVIEW
2.1 Review of Related
Works……...…………..……………………………..…………
…….5
2.2 Voltage
Stability…………...……….……………………………………
……...………...8
2.3 Voltage
Collapse…..………………………………………………………
……..………..8
2.4 Flexible Alternating Current Transmission System
(Facts)...………………….……….....9
2.5 Facts Compensating Devices
………………………………………………...…………..11
2.5.1 Static Synchronous Compensator
(STATCOM)………………..……………....11
2.5.2 Thyristor-Switched Series Capacitor
(TSSC)…………………………………..12
2.5.3 Static Synchronous Series Compensator
(SSSC)……………………………….13
2.5.4 Thyristor-Controlled Series Capacitor
(TCSC)…………………………………14
2.6 Unified Power Flow Controller
(UPFC)…………………………………………………..15
CHAPTER THREE: METHODOLOGY
3.1 Location of
UPFC……………………..…………………………….………
…………….21
3.2 Newton Raphson Load Flow Method
…………..………………………………………...22
3.2.1 Formation of the Y-
Bus………………………………………………………….23
3.2.2 Forming the Jacobian
Matrix…………………………………………………....25
3.3 Incorporating the UPFC in Newton Raphson Load
Flow……………….…………...…....26
CHAPTER FOUR: SIMULATION AND RESULTS
ANALYSIS
4.1 Case
1………………………………………………….………………
…………………..29
4.2 Case
2……………..……………………………………………………
………………….30
CHAPTER FIVE: CONCLUSION AND
RECOMMENDATION
5.1
Conclusion………….……………………………………………
…….………………….34
5.2
Recommendations...……….………….…………………………
…………………….…..35
APPENDIX A
…………………..….……………………………………………
…………...36
REFERENCES…………..……………………………………
……………………………..40
LIST OF FIGURES
Figure2.1 Overview of the main FACTS
Devices…………………………………..10
Figure2.2 A static synchronous
compensator……………………………………….12
Figure2.3 (a) Circuit diagram of a TSSC, (b) Course of capacitor
voltage for
the basic element in a
TSSC………………………………………………………..13
Figure2.4 (a) A two machine system with a series capacitor
compensated line, (b) its associated phasor
diagram…………………………………………………………
……………14
Figure2.5 Thyristor-Controlled Series Capacitor
(TCSC)…………………………..15
Figure2.6 Schematic diagram of the
UPFC…………………………………………17
Figure2.7 Concept of the UPFC in a two-machine power
system…………………..18
Figure2.8 Implementation of
UPFC…………………………………………………19
Figure3.1 One line diagram of the power system
model…………………………….21
Figure3.2 A two bus system for illustrating Newton Raphson
Power flows………...24
Figure3.3 Unified power flow controller equivalent
circuit………………………....26
Figure 4.1 Voltages of the buses without the UPFC between
buses 3 and 4………...29
Figure 4.2 Voltages of the buses with the UPFC between buses 3
and 4……………31
LIST OF TABLES
Table 2.1 FACTS Applications and cost
Comparison………………………………20
Table 4.1 Bus voltages without the
UPFC…………………………………………..29
Table 4.2 Line Flows and Losses without
UPFC……………………………………30
Table 4.3 Bus voltages with
UPFC…………………………………………………..30
Table 4.4 Line Flows and Losses with UPFC
………………………………………..31
Table 4.5 voltages of the buses with and without the UPFC
between buses
3 and
4…………………………………………………………………
…………….32
Table 4.6 Bus Data: IEEE 5 Bus
System…………………………………………….33
Table 4.7 Line Data for IEEE 5
Bus…………………………………………………33
i
CHAPTER ONE
INTRODUCTION
1.1 BACKGROUND OF THE STUDY
For electric utilities as well as users, the high cost of electricity
has taken on greater significance. Disturbances on the utility and
customer sides cause transients, waveform distortions, and
terminal voltage variations on the electric grid, which ultimately
lead to a power quality issue. The term "maintaining the
waveforms of voltages and currents as sinusoidal at rated
frequency and magnitude" relates to power quality, or PQ. Due
to the advent of equipment with power electronic devices, which
are more susceptible to power quality issues, power systems
sustaining power quality has recently become the most critical
issue (Asha Kiranmai, 2010). The rising usage of non-linear
loads, such as electronic control gears, variable speed drives,
and power electronic equipment, is what most affects power
quality. The safe, dependable, and effective functioning might be
impacted by poor power quality. Voltage sag, voltage swell,
voltage fluctuations, voltage unbalance, harmonics, etc. are
some of the elements of power quality. Power electronic
devices, such Flexible AC Transmission Systems (FACTS) and
custom power devices, have opened up new avenues for power-
quality improvement by introducing an expanding field of
technology that gives the power system more flexible new
control capabilities.
To reduce electricity costs, the current power system is
deregulated, meaning that generation, transmission, and
distribution are handled by separate entities. With the increasing
demand for electric power, it is crucial to make full use of
existing generating units, push transmission lines to their
thermal limits, and maintain system stability. Additionally, it is
important to minimize losses in the transmission lines. Flexible
AC Transmission System (FACTS) devices are vital for
controlling power flow and boosting the capacity of existing
lines. These devices use power electronics to improve
controllability and increase power transfer capability. FACTS
technology could enable smarter electric transmission systems in
the future.
FACTS controllers include devices such as the Static
Synchronous Compensator (STATCOM), Thyristor Controlled
Series Capacitor (TCSC), Static Series Synchronous
Compensator (SSSC), and Static VAR Compensator (SVC).
These controllers are capable of rapidly adjusting network
conditions to enhance voltage stability and power quality.
Voltage instability arises when the system cannot meet the
reactive power demand, which can occur during faults, heavy
loading, or voltage fluctuations. FACTS devices can correct
reactive power imbalances by injecting or absorbing reactive
power as needed to stabilize the system (Mohanty, Ahamad, and
Khan, 2013).
The Unified Power Flow Controller (UPFC) is the most versatile
device among the Flexible AC Transmission Systems (FACTS).
It integrates the functions of multiple devices, including the
Static Synchronous Compensator (STATCOM), Thyristor
Switched Capacitor (TSC), Thyristor-Controlled Reactor (TCR),
and Phase Angle Regulator. Additionally, the UPFC offers
enhanced flexibility by combining select functions of these
devices (Mathad, Basanagouda, 2014). The primary purpose of
the UPFC is to regulate real and reactive power flow by
injecting voltage in series with the transmission line, allowing
independent control of voltage magnitude and phase angle. This
enables power flow control in designated routes and optimal
loading of transmission lines, approaching their thermal limits.
Furthermore, UPFCs are employed to enhance the transient and
small signal stability of the power system.
1.2 STATEMENT OF PROBLEM
A power system's characteristics change over time as a result of
growing loads and the addition of additional generation
capacities. In both steady-state and transient scenarios, the
power system is susceptible to stability problems in the absence
of appropriate modifications to the transmission infrastructure.
Reduced stability margins restrict power transfer capabilities
and reduce transmission efficiency. Historically, building new
transmission and generation infrastructure was necessary to
meet these restrictions. These initiatives can, however, be costly,
time-consuming, and fraught with environmental and regulatory
issues. Using Flexible AC Transmission Systems (FACTS)
technology, like the Unified Power Flow Controller (UPFC), is
an alternate approach that can improve system performance
without requiring significant alterations to the current
infrastructure.
The UPFC plays a major role in enhancing power flow and
voltage profile controllability within the power system network.
It can minimize system instability, optimize power flows
dynamically, and control voltage stability. By deploying UPFC
devices strategically at network nodes, operators can make the
most of existing transmission facilities without having to make
major infrastructure modifications. They are able to efficiently
modify and control voltage profiles and power flow patterns as a
result. Creating and implementing control methods that make
the most of the Unified Power Flow Controller's (UPFC)
capabilities is the difficult part. In order to ensure overall system
efficiency and dependability, as well as appropriate power flow
and voltage stability, sophisticated modeling, simulation, and
real-time control approaches are needed.
UPFC technology provides a cost-effective and efficient way to
improve power system performance by offering enhanced
flexibility and control over power flow and voltage profiles.
This project focuses on exploring effective ways to leverage
UPFC technology to meet these objectives, addressing the
evolving challenges and demands of contemporary power
systems.
1.3 JUSTIFICATION OF THE STUDY
This research initiative is justified by its potential to supply a
clean, sustainable, and dependable energy source for educational
and scientific endeavors.
1.4 AIM
The aim of this research is to Utilize/Implement a unified power
flow controller (UPFC) for improvement of voltage stability in a
congested electric network
1.5 OBJECTIVE
Its specific objectives are to
1. Develop mathematical models for transmission systems and
UPFC, which can to be blended together, coded, and used
extensively.
2. Illustrate the controllable features of UPFC in active and
reactive power flows in a transmission line.
3. Maintain the nodal voltage magnitudes in a power system
in the limit for system security
1.6 SCOPE OF STUDY
The limits and scope of this study's investigation into the
Unified Power Flow Controller (UPFC) implementation for
enhancing voltage stability in a crowded electric network are
specified. It describes the particular areas of emphasis, the
approaches used, the constraints, and the project's anticipated
results.
1.7 LIMITATIONS
Scope of Network Model: This study uses a simplified model
of a congested electric network, which may not capture all
complexities of real-world systems.
Simulation Constrains: Results are based on simulations and
may differ in actual field implementations due to unforeseen
factors.
Focus on UPFC: The study is limited to the UPFC only and
does not consider other FACTS devices or alternative
technologies.
1.8 THESIS ORGANIZATION
This thesis is organized into the following chapters:
Chapter 1: Introduction: Provides an overview of UPFC,
introduces the research objectives, and outlines the structure of
the thesis.
Chapter 2: Literature Review: Reviews relevant literature on
UPFC technology, applications, and previous research studies.
Chapter 3: Methodology and Simulation Tools: Describes the
methodology used for modeling UPFC, selection of simulation
tools, and validation techniques.
Chapter 4: Results and Analysis: Presents the results of UPFC
simulation studies and provides detailed analysis of the findings.
Chapter 5: Conclusion and Recommendations: Summarizes the
key findings, discusses implications, and provides
recommendations for future research and practical
implementation.
CHAPTER TWO
LITERATURE REVIEW
2.1 REVIEW OF RELATED WORKS
A Flexible Alternating Current Transmission System (FACTS)
can improve control over power flow, secure loading, and
reduce power system oscillations by using power electronic
controllers. A variety of power electronic systems are included
in FACTS, such as the Unified Power Flow Controller (UPFC),
Thyristor-Controlled Series Capacitor (TCSC), Static Condenser
(STATCON), and Static VAR Compensator (SVC). One flexible
power electronic system that provides phase angle adjustment,
line impedance management, and VAR correction is the Unified
Power Flow Controller (UPFC). It consists of two fully
regulated power electronic converters that, by varying the
injected voltage's magnitude and phase angle, allow for quick
adjustment of the actual and reactive power flow in the
transmission line.
Laszlo Gyugyi and Fellow (1994) developed a
revolutionary solution to real-time power flow regulation and
dynamic correction in transmission systems using solid-state
synchronous voltage sources. Using ate turn-off (GTO)
thyristors, a multi-pulse inverter creates the synchronous voltage
source. It can negotiate real power exchange with the ac system
by interacting with an appropriate energy storage device in
addition to being able to generate the reactive power required for
network compensation internally. They created a thorough
description of phase angle control, series compensation, and
shunt compensation for solid-state synchronous voltage sources
used in power flow management. It also describes the unique
unified power flow controller that is able to control concurrently
or selective all three network parameters (voltage, impedance,
transmission angle) determining power transmission.
In (1995) Gyqyi, and et al. described the basic concepts of
the proposed generalized P and Q controller and compares it to
the more conventional, but related power flow controllers, such
as the thyristor-Controlled Series Capacitor and Thyristor-
Controlled Phase Angle Regulator. And they also present results
of computer simulations showing the performance of the UPFC
under different system conditions.
In (1996) Round, and et al. studied the performance of a
unified power flow controller (UPFC) with four different
controllers and evaluated through simulation and
implementation in an experimental laboratory model. The
controllers which were investigated are the PI controller, PI
controller with decoupling, cross-coupling controller and robust
H∞ controller. It is found that the cross- coupling and Robust
H∞ controllers have the best performance when the exact value
of the power transmission parameters is unknown.
In (1997) M. Noroozian, et al. deal with optimal power
flow control in electric power systems by use of unified power
flow controller (UPFC). And they developed and analyzed
Models suitable for incorporation in power flow programs. And
demonstrated the application of UPFC for optimal power flow
control through numerical examples. It is shown that a UPFC
has the capability of regulating the power flow and minimizing
the power losses simultaneously.
In (2000) Zhengyu Huang, et al. discuss four principal
main control strategies and the computer tests results support the
discussion conclusion and also, they concluded the constant
power flow control is good for steady state control and the
constant series compensation control is useful for first swing
stability. The supplementary control is very efficient in damping
the power oscillation. The suggested UPFC control can realize
the desired control strategy flexibly and improve system
dynamic performance significantly.
In (2010) Muthukrishnan and Nirmal Kumar dialed with
digital simulation and implementation of power system using
UPFC to improve the power quality. They deduce that UPFC is
also capable of improving transient stability in a power system.
In (2010), Mathukrishanan and nirmalkumar dialed with digital
simulation of 14 – bus power system using UPFC to improve the
power quality, they conclude that the UPFS has the capability of
improving the transient stability in a power system.
In (2010) Murali, and et al. investigates the improvement of
transient stability of a two-area power system using UPFC and
simulations are carried out in Matlab/Simulink environment for
the two-area power system model with UPFC to analyze the
effects of UPFC on transient stability performance of the
system. The performance of UPFC is compared with other
FACTS devices such as Static Synchronous Series Compensator
(SSSC), Thyristor Controlled Series Capacitor (TCSC), and
Static Var Compensator (SVC) respectively. The simulation
results demonstrate the effectiveness and robustness of the
proposed UPFC on transient stability improvement of the
system.
In (2011) Arup Ratan Bhowmik and Champa Nandi
investigated the performance of Unified Power Flow Controller
(UPFC) in controlling the flow of power over the
transmission line and they dialed with digital simulation of
standard IEEE 14-bus power system using UPFC to improve the
real and reactive power flow control through a transmission line
by placing UPFC at the sending end using computer simulation.
In (2012) Aarti Rai includes first the optimal location of
FACTS devices, second voltage stability analysis and third
control of reactive power of system. The model can be simulated
in MATLAB. The performance of the whole system such as
voltage stability, transient stability, frequency and power swings
will be analyzed and compared without FACTS and with
FACTS device.
In (2013) Rama Sekhara Reddy and Vijaya Kumar used a
Unified Power Flow Controller (UPFC) to control the power
flow in the transmission systems by controlling the impedance,
voltage magnitude and phase angle in wind energy generation.
This controller offers advantages in terms of static and dynamic
operation of the power system.
In (2013) Kumar Gaurav and Nitin Saxena conducted an
investigation on the enhancement in voltage stability margin as
well as the improvement in the power transfer capability in a
power system with the incorporation of UPFC. A simple
transmission line system is modeled in Matlab/Simulink
environment. The load flow results are first obtained for an
uncompensated system, and the voltage and power profiles are
studied. The results so obtained are compared with the result
obtained after compensating the system using UPFC to show the
voltage stability margin enhancement.
In (2013) Vaibhav S Kale et, al. proposed the real, reactive
power and voltage control through a transmission line by
placing UPFC at the sending end using computer simulation.
The control scheme has the fast-dynamic response and hence is
adequate for improving transient behavior of power system after
transient conditions [19].
In (2013) K.Ravichandrudu and et al. introduced the
concept of Distributed FACTS (D-FACTS) as an alternative
approach to realizing cost-effective power flow control. They
concluded that the UPFC is capable of improving transient
stability in a power system and it is the most complex power
electronic system for controlling the power flow in an electrical
power system. The circuit model is developed for UPFC using
rectifier and inverter circuits. The control angle is varied to vary
the real and reactive powers at the receiving end.
K.Ravichandrudu also demonstrated the performance of the
UPFC in achieving harmonic mitigation and stability of the
wind energy grid connected system by using
MATLAB/SIMULINK.
In (2014) B.Gopinath et, al. proposed a method based on
Model predictive control (MPC) and using Bacterial Forging
Algorithm (BFA) for modeling Unified Power Flow Controller.
Modeling of UPFC is designed with its unique capability to
control simultaneously real and reactive power flows on a
transmission line as well as to regulate voltage at the bus where
it is connected. Therefore, this device creates a remarkable
quality impact on power system stability. UPFC with additional
PI controller is used along with the UPFC main controller for
this purpose. The simulation is carried out in
MATLAB/simulink.
In (2015) Koganti et, al. studied Power quality and stability
improvement of HVDC transmission System using UPFC for
different uncertainty conditions, they concluded that UPFC
improves the system performance. It can control the power flow
in the transmission line, effectively. With the addition of UPFC,
the magnitude of fault current reduces and oscillations of
excitation voltage also reduce. The total harmonic distortion
(THD) is also reduced well below the IEC standards. It is more
economical for the HVDC transmission system to transfer more
power.
In (2015) Shantha Soruban et, al. proposed an ANN based
control scheme for a UPFC to be used as an active power filter.
The objective is to guarantee power to the load at the required
power quality. The ANN control unit monitors the voltage at the
point of common coupling. UPFC enables improved power
quality by maintaining power factor nearer to unity rapid
response time, the ability to provide reactive power at low
voltage and to provide voltage compensation can be obtained.
For unbalanced voltage compensation, two unbalanced
controllers using the phase voltage amplitude and negative
sequence component are proposed.
In (2015) G. Srinivas and T. Santosh Chaitanya studied and
analyzed the operation and performance of D-STATCOM to
compensate the harmonics coming from grid side inverter and
different loads in that most of the unbalanced and +nonlinear
loads inject harmonic currents to source side and effects the
source. This can be overcome by using D-STATCOM by
connecting as shunt at the distribution side by means of a tie
reactance connected to compensate the load current.
This chapter presents a sum of papers that used a UPFC to
improving the active and reactive power flow of the power
systems.
2.2 VOLTAGE STABILITY
Many journals and other publications have looked into the idea
of reactive power compensation and voltage stability.
Additionally, several writers and researchers have presented
several approaches to reactive power compensation, ranging
from traditional to fast-acting thyristor-based compensating
systems. The ability of a power system to sustain constant,
acceptable voltages at each bus in the system both during regular
operation and following a disturbance is known as voltage
stability. When a disturbance, rise in load demand, or
modification in system conditions results in a gradual and
uncontrollable reduction in voltage, the system enters a state of
voltage instability. The primary cause of instability is the power
system's incapacity to supply reactive power at the required rate.
Usually, the voltage drop that happens when reactive and active
power pass through the transmission network's inductive
reactance is the main cause of the issue. These occurrences
might cause the generators to become out of sync, which would
further destabilize the system. (P. Kundur, 2012).
2.3 VOLTAGE COLLAPSE
Voltage collapse remains a significant challenge for power
system networks. Voltage collapse can be either total blackout,
or partial. A major factor contributing to voltage collapse is the
inadequacy of reactive power resources in the system. As system
loads increase, voltages across the network tend to drop, and
reactive power losses rise due to high current, with these losses
being proportional to the square of the current. To counteract
this increased reactive power demand, voltage-regulating
devices such as generators, static VAR compensators, and
capacitors are employed, if available (Anderson and Fouad,
2008).
Due to inherent physical constraints, reactive power devices
cannot provide unlimited reactive power. As electrical loads
increase over time, these devices or multiple sources may reach
their maximum capacity. When a reactive power source hits its
limit, it can no longer maintain voltage regulation. This leads to
accelerated voltage decline, necessitating even more reactive
power. This increased demand can push additional voltage-
regulating devices to their limits, further speeding up the voltage
drop. This situation can cause a significant portion of the system
to experience voltage loss, culminating in a voltage collapse.
2.4 FLEXIBLE ALTERNATING CURRENT TRANSMISSION SYSTEM
(FACTS)
Power electronics is a proven technology that has transformed
every facet of the electrical power network, impacting not only
the distribution, utilization, and transmission of AC power but
also the transmission of high voltage direct current (HVDC) (X.
Jiang, 2010).
In order to achieve electronic controllability, the Flexible AC
Transmission Systems (FACTS) concept makes considerable use
of power electronic devices on the high-voltage side of the
network. Electric Power Research Institute (EPRI) introduced
FACTS in the 1980s; it capitalizes on advances in high-voltage
and high-current power electronics (Narain G, 2000). Both
steady-state and transient performance are improved by this
method, which also improves control over power flows in the
high-voltage section of the network. The design and
construction of power plant equipment, as well as the planning
and management of transmission and distribution networks, are
being affected by the shift to electronic controllability.
Because they allow for quick control over energy flow
pathways, these advances are predicted to completely transform
energy transactions. FACTS has garnered substantial backing
from electrical equipment makers, utilities, and research
institutions worldwide, owing to its noteworthy economic and
technological advantages (P. Therond, 1994).Globally, a variety
of FACTS controllers have been put into practice, each with a
specific purpose in mind to maximize power system efficiency
and operation: load tap changers, phase-angle regulators, static
VAR compensators, thyristor-controlled series compensators,
interphase power controllers, static compensators, and unified
power flow controllers (P. Zhang, 2012).
FACTS devices introduce a wide operational range to increase
the thermal limits of a power system and improve its stability.
FACTS devices have been used for:
• Active and reactive Power control
• Voltage control stability and Sub synchronous resonance
mitigation
• Power oscillation damping
• Transients and dynamics stability
• Fault current limiting
• Flicker mitigation
• Power system security enhancement
Fig 2.1 Overview of the main FACTS Devices
2.5 FACTS DEVICES
Within limited bounds, conventional devices provided
satisfactory results. But given the substantial changes taking
place in the power sector and the rising demand for electricity,
power system operators must look into more efficient ways to
run the system. This entails controlling energy flow pathways
quickly in order to make the most use of the transmission
infrastructure that is already in place. By utilizing cutting-edge
power electronic tools and techniques, also known as Flexible
AC Transmission Systems (FACTS), this objective is
accomplished.
The following section examines how FACTS devices serve as
promising solutions for reactive power compensation.
2.5.1 STATIC SYNCHRONOUS COMPENSATOR (STATCOM)
One device in a family of devices known as flexible AC
transmission system (FACTS) devices is the solid-state shunt
device STATCOM, which produces or absorbs reactive power.
According to A. Suul (2010), the STATCOM and SVC are
comparable in terms of response time, controllability, and power
electronics utilization. The STATCOM synthesizes the reactive
power output utilizing self-commutated power electronics as
opposed to traditional capacitors, inductors, and thyristors. As a
result, output capability is often symmetric, offering an equal
amount of capacity for absorption and production. Because the
STATCOM is solid-state, its controls can be built to give highly
fast and efficient voltage control, just like the SVC. Although
synchronous condensers and generators can handle short-term
overloads better than STATCOM capacity, SVCs and capacitors
are more severely affected by voltage degradation. Due to their
current limitation, STATCOMs' MVAR capability reacts to
voltage linearly as opposed to SVCs and capacitors' voltage-
squared connection. This feature makes STATCOMs much more
effective in averting voltage collapse.
Figure2.2 A static synchronous compensator
2.5.2 THYRISTOR-SWITCHED SERIES CAPACITOR (TSSC)
A bypass valve switches a capacitor, which is the fundamental
component of a TSSC. If the matching thyristor valve is closed,
the capacitor is connected into the line; if not, it is bypassed.
When the current crosses zero, a thyristor valve is closed.
Therefore, only at the zero crossings of the line current can the
thyristor valve insert the capacitor into the line. However, in
order to reduce the first surge current in the valve and the
associated circuit transient, the thyristor valve should only be
activated for bypass when the capacitor voltage is zero. As a
result, turning on the valve may take up to one complete cycle
longer. Consequently, after the capacitor is placed in the line, the
line current will charge it from zero to the maximum during the
first half cycle and discharge it from the maximum to the zero
during the next half cycle, or until the capacitor can be bypassed
once more (IEEE, 2004). This can be seen in Fig. 2.3 (b). In
series with the line reactance, the TSSC can be thought of as a
controllable reactance. The line's compensation degree can be
determined by dividing the line reactance by the ratio of the
TSSC reactance that was introduced.
(a)
(b)
Figure2.3 (a) circuit diagram of a TSSC, (b) course of
capacitor voltage for the basic element in a TSSC
2.5.3 STATIC SYNCHRONOUS SERIES COMPENSATOR (SSSC)
To control the transmitted electric power, a static synchronous
generator that is powered by an internal electric energy source
can be used as a series compensator. Its output voltage can be
adjusted independently of the line current and is in quadrature
with it. This allows the generator to adjust the overall reactive
voltage drop across the line. In order to improve the power
system's dynamic behavior, the SSSC may incorporate energy-
absorbing or transiently rated energy storage devices. These can
be used to temporarily raise or lower the total active (resistive)
voltage drops across the line.
For a better understanding, the basic working principles of the
SSSC can be stated in terms of the traditional series capacitive
compensation. The two machine systems with a traditional
series capacitor and a basic comprehension of its phasor diagram
are depicted in Figure 2.4. The above phasor diagram
demonstrates how, at a certain line current, the series capacitor's
voltage pushes the series line reactance's opposite polarity
voltage to increase by the capacitor voltage's magnitude.
Thus, in order for the series capacitive compensation to
function, the voltage across the physical line's line impedance
must be increased. This raises the corresponding line current and
transmitted power. Figure 2.4 displays the voltage drop across
the capacitor (VC) and the voltage drop across the line (VL),
along with the line current (I). The phasor diagram indicates the
magnitude of the sending and receiving end voltages (VS and
VR), the reactance of the line (XC) and the capacitor (XL), and
the angle between the two end source voltages (δ).
(a)
(b)
Figure2.4 (a) A two machine system with a series capacitor
compensated line, (b) its associated phasor diagram
Thus the power flow in the line is increased by controlling the
reactance of the line using series compensation as shown in
equation 2.1
(2. 1)
2.5.4 THYRISTOR-CONTROLLED SERIES CAPACITOR (TCSC)
A series compensator is the fundamental component of a
Thyristor Controlled Series Capacitor (TCSC). Multiple of these
compensators can be linked in series to provide the required
voltage rating and operating characteristics. This configuration
is comparable to the TSSC's, and it may be turned on and off in
the same way as the TSSC if the reactor's impedance (XL) is
low enough compared to the capacitor's (XC).
The fundamental principle of the TCSC scheme is to partially
negate the TCR's effective compensating capacitance in order to
provide a continuously changing capacitor. Equation 2.5
displays the equivalent impedance of the TCSC. At the
fundamental frequency, the TCR may have a continuously
variable reactive impedance that is controllable by a delay angle.
The steady-state impedance of the TCSC is that of a parallel LC
circuit, made up of a variable inductive impedance (XL) and a
fixed capacitive impedance (XC) (Sindekar and Parate, 2012).
(2. 2)
The scheme of a Thyristor-Controlled Series Capacitor is given
in Fig. 2.5. A parameter to describe the TCSC main circuit is λ
which is the ratio of the resonant frequency (fr) and the network
frequency (f) resulting in
. (2.
3)
(2.
4)
(2.
5)
For the LC circuit, the resonant frequency is given by
. (2.
6)
substituting equations 2.4 and 2.5 into 2.6, we have
. (2. 7)
Figure2.5Thyristor-Controlled Series Capacitor (TCSC)
2.6 UNIFIED POWER FLOW CONTROLLER (UPFC)
Overview
The Unified power flow controller (UPFC) concept was
proposed by Gyugyi in 1991.in the late 1980s, the Electric
Power research Institute (EPRI) formulated the Flexible AC
transmission voltage and power flow and reduces dynamic
disturbances.
Power flow over a transmission system is limited by some
followings:
• System stability
• Loop flows
• Voltage limits
• Thermal limits of either lines or terminal equipment
• High short circuit level limits
Such transmission on power transfer are primarily due to the
lack of high–speed control of inter related electrical parameters
including voltage, current, impedance, phase angle, reactive and
active power. FACTS controllers enhance the value of AC
transmission assets by controlling any one or more of these
parameters.
Makombe and Jenkins, experimentally proved that a UPFC can
control the three control parameters either individually or in
appropriate combinations at its series-connected output while
maintaining reactive power support at its shunt connected input
device is to enhance the useable transmission capacity of lines
and control the power flow.
The third generation of FACTS devices, known as the Unified
Power Flow Controller (UPFC), is by far the most
comprehensive. It can implement power flow regulation in a
steady-state power system, reasonably control line active power
and reactive power, and improve the power system's
transmission capacity. In a transient power system state, it can
realize fast-acting reactive power compensation, dynamically
support the voltage at the access point, and improve system
voltage stability. In addition, it can improve power angle
stability and damping of the system.
The UPFC makes use of solid-state devices, which offer
functional flexibility that traditional thyristor-controlled systems
typically cannot match. A common DC voltage link connects a
static synchronous compensator (STATCOM) and a static
synchronous series compensator (SSSC), which together form
the UPFC.
Controlling the fluxes of both active and reactive power in the
transmission line is the primary benefit of the UPFC. The UPFC
will not function if the source side has any disruptions or
malfunctions. Only a balanced sine wave source can run the
UPFC. Phase angle, voltage, and reactance in the line are the
UPFC's controllable parameters. L. Gyugyi of Westinghouse
first presented the UPFC concept in 1995. A secondary but
crucial function that the UPFC enables is stability control, which
reduces power system oscillations and increases the power
system's transient stability.
In a publication titled "Power Quality Enhancement of Standard
IEEE 14 Bus System using Unified Power Flow Controller," S.
S. Khonde, S. S. Dhamse, and A. G. Thosar state that the unified
power flow controller (UPFC) combines the characteristics of
three compensators—phase angle, voltage magnitude, and
impedance—to create a more comprehensive compensation.
through adjusting phase angle, voltage magnitude, and
impedance. The power flow in the transmission networks is
managed by the unified power flow controller (UPFC).
Two voltage source converters—series and shunt converters—
that are linked to one another via a common dc link make up the
UPFC. While the series converter, also known as the Static
Synchronous Series Compensator (SSSC), is used to add
controlled voltage magnitude and phase angle in series with the
line, the shunt converter, also known as the Static Synchronous
Compensator (STATCOM), is used to provide reactive power to
the ac system. In addition, it will provide the dc power required
for both inverters. Power electronic converters and transformers
are found in every branch. There was a common DC capacitor
between these two voltage source converters. This DC capacitor
typically has a limited ability to store energy.
As a result, the active power produced by the series converter
and the active power drawn by the shunt converter must match.
Greater control over power flow is possible due to the
independent selection of reactive power in the shunt or series
converter. The gadget is connected to the system via the
coupling transformer.
Fig 2.6 Schematic diagram of the UPFC
One major development in the field of Flexible AC
Transmission Systems (FACTS) is the Unified Power Flow
Controller (UPFC). Precise control over voltage and power flow
in AC transmission lines is achieved through the use of
sophisticated power electronic components. By dynamically
modifying line impedance and voltage parameters, UPFC plays
a crucial part in optimizing grid performance and enhancing
transmission stability and efficiency. This capacity is essential
for improving grid reliability, reducing traffic, and making it
easier to integrate renewable energy sources. Due to its
adaptability and efficiency, UPFC is now widely used in power
systems, helping to facilitate the continuous development of
electrical grids that are more intelligent and resilient.
The UPFC was created for dynamic compensation and real-time
control of AC transmission systems. It has the ability to regulate
every aspect of the transmission line's power flow. As an
alternative, it has the ability to separately regulate the line's
reactive and active power flows. In theory, the UPFC is a
synchronous voltage source that is connected in series with the
line and has programmable magnitude and angle. Both active
and reactive power are exchanged between the voltage source
and the transmission system. However, the voltage source is
only able to generate reactive power; a power source or sink
must provide it with active power. A power supply is a type of
end bus.
Currently, a UPFC is made up of two voltage-source converters
that are powered by a common DC link and arranged back to
back (DC storage capacitor). In Figure 2.7, this implementation
is displayed.
Figure2.7 Concept of the UPFC in a two-machine power
system
Between the converters' AC terminals, active power can move
freely in either way, and each converter has the ability to
independently produce and absorb reactive energy. As the
voltage source, Converter 2 injects the voltage, which is tunable
in both amplitude and phase, in series with the line.
The converter internally generates the reactive power that is
transferred at the AC terminal. In contrast, the active power is
transformed into DC power, which manifests as a positive or
negative active power demand at the DC connection. Converter
1 transforms this DC power requirement into AC power, which
is then connected to the transmission line bus through the supply
transformer. Furthermore, converter 1 can supply independent
shunt reactive compensation for the line and, if needed,
exchange reactive power with the line.
Figure2.8 Implementation of UPFC
Table 2.1 FACTS Applications and cost Comparison
Because it can manage all the parameters that affect the
transmission line power flow, such as voltage, phase angle, and
impedance, UPFC, one of the FACTS devices listed in Table
2.1, can cover all the specified applications (N. Hingorani & L.
Gyugyi, 2000).
CHAPTER THREE
METHODOLOGY
This chapter's task is to examine the modeling and simulation
techniques utilized for the power system network as well as the
UPFC models that regulate the system's bus voltages. It also
provides a thorough mathematical representation of the
simulations' used solutions.
One-line diagram of the power system used as the model for this
project work is
shown in figure the figure below.
Figure3.1: One line diagram of the power system model
3.1 LOCATION OF UPFC
UPFC must be installed in the correct places for the system to
have higher voltage stability. The weak busses in the system
were identified by a load flow analysis, which helped select the
ideal position. Although there are other approaches for studying
load flow, the Newton Raphson method has shown to be the
most effective because of its robust convergence properties.
Therefore, it was applied in this project to ascertain the steady
state voltages at each of the system's busses.
3.2 NEWTON RAPHSON LOAD FLOW METHOD
This approach uses iteration to solve the following set of
nonlinear algebraic equations.
(3.
1)
where F represents the set of ‘n’ nonlinear equations, and X is
the vector of ‘n’ unknown state variables.
The essence of the method consists of determining the vector of
state variables X by performing a Taylor series expansion of
F(X) about an initial estimate X (0):
higher-order terms (3. 2)
where J(X (0)) is a matrix of first-order partial derivatives of
F(X) with respect to X,
termed the Jacobian, evaluated at X=X (0
).
This expansion lends itself to a suitable formulation for
calculating the vector of state variables X by assuming that X (1)
is the value computed by the algorithm at iteration 1 and that
this value is sufficiently close to the initial estimate X (0
). Based
on this premise, all high-order derivative terms in Equation (3.2)
may be neglected. Hence
+ (3. 3)
In compact form, and generalising the above expression for the
case of iteration (i),
(3. 4)
where i = 1, 2 . . . .
Furthermore, if it is assumed that X(i
) is sufficiently close to the
solution X(*), then FX(i
) ≈ FX(*) = 0. Hence, equation (3.4)
becomes
(3. 5)
and solving for X(i
),
(3. 6)
The iterative solution can be expressed as a function of the
correction vector
ΔX(i)= X(i) - X(i -1),
(3. 7)
and the initial estimates are updated using the following relation:
(3. 8)
The calculations are repeated as many times as required using
the most up-to-date values of X in equation (3.7). This is done
until the mismatches ΔX are within a prescribed small tolerance
(i.e. 1e -12).
The essential equations must be represented in the form of
Equation (4.7), where X is the set of unknown nodal voltage
magnitudes and phase angles, in order to apply the Newton
Raphson approach to the power flow problem. The power flow
Newton Raphson algorithm can be described by the following
connection since the power mismatch equations ΔP and ΔQ are
enlarged around a base point (θ(0), V(0)):
(3. 9)
The various matrices in the Jacobian may consists of up to (nb -
1) × (nb - 1) elements of the form:
(3. 10)
where nb is the number of buses with the slack bus entries
removed, and k and m are the values of 1,..., and nb,
respectively. Additionally, the rows and columns for PV buses
that relate to reactive power and voltage magnitude are removed.
Moreover, the matching k–m item in the Jacobian is null when
buses k and m are not connected directly by a transmission
element. Because real power networks have relatively modest
levels of connectedness, power flow Jacobians are quite sparse.
They have the trait of being symmetrical in structure but not in
value. extra
Note that the correction terms ΔVm are divided by Vm in order
to offset the multiplication of the Jacobian terms (∂PK/∂Vm)Vm
and (∂QK/∂Vm)Vm by Vm. The derivative terms provided
below demonstrate how this trick produces helpful calculations
that can be made simpler.
Figure3. 2: A two bus system for illustrating Newton Raphson
Power flows
Consider the element connected between buses k and m in
Figure 3.2, for which self and mutual Jacobian terms are given
below:
3.2.1 FORMATION OF THE Y-BUS
In order to develop suitable power flow equations, it is
necessary to find relationships between injected bus currents and
bus voltages. Based on Figure 3.2 the injected complex current
at bus k, denoted by IK, may be expressed in terms of the
complex bus voltages Ek and Em as follows:
(3.1
1)
Similarly for bus m,
(3.1
2)
The above equations can be written in matrix form as,
(3.1 3)
or
(3.1 4)
where the bus admittances and voltages can be expressed in
more explicit form:
(3.1 5)
(3.1 6)
where i = k, m; j = k, m
The complex power injected at bus k consists of an active and a
reactive component and may be expressed as a function of the
nodal voltage and the injected current at the bus:
(3.1 7)
where IK is the complex conjugate of the current injected at bus
k.
The expressions for and can be determined by substituting
equations 3.15
and 3.16 into equation 3.17, and separating into real and
imaginary parts
(3.1 8)
(3.1 9)
Equations 3.18 and 3.19 are the two important power flow
equations and are used in deriving the Jacobian matrix.
3.2.2. FORMING THE JACOBIAN MATRIX
For k ≠ m,
(3.20)
(3.21)
(3.22)
(3.23)
For K = m,
(3.24)
(3.25)
(3.26)
3.3 INCORPORATING THE UPFC IN NEWTON
RAPHSON LOAD FLOW
Figure3. 3:Unified power flow controller equivalent circuit
The UPFC voltage sources are:
(3.27)
(3.28)
where and are the controllable magnitude ( ) and phase angle (
2) of the voltage source representing the shunt converter. The
magnitude and phase angle of the voltage source representing
the series converter are controlled between limits ( and ( 2),
respectively.
The phase angle of the series-injected voltage determines the
mode of power flow control. If is in phase with the nodal
voltage angle, the UPFC regulates the terminal voltage. If is in
quadature with respect to , it controls active power flow, acting
as a phase shifter. If is in quadrature with the line current angle
then it controls active power flow, acting as a variable series
compensator. At any other value of , the UPFC operates as a
combination of voltage regulator, variable series compensator,
and phase shifter. The magnitude of the series-injected voltage
determines the amount of power flow to be controlled.
Based on the equivalent circuit shown in figure 3.3 and
equations (3.27) and (3.28), the active and reactive power
equations at bus k are:
(3.29)
(3.30)
at bus m:
(3.31)
(3.32)
Series converter:
(3.33)
(3.34)
Shunt converter:
(3.35)
(3.36)
Assuming loss-less converter valves, the active power supplied
to the shunt converter, , equals the active power demanded by
the series converter, ; that is,
Furthermore, if the coupling transformers are assumed to
contain no resistance then the active power at bus k matches the
active power at bus m. Accordingly,
The UPFC power equations, in linearized form, are combined
with those of the AC network. For the case when the UPFC
controls the following parameters: (1) voltage magnitude at the
shunt converter terminal (bus k), (2) active power flow from bus
m to bus k, and (3) reactive power injected at bus m, and taking
bus m to be a PQ bus, the linearized system of equations is as
follows:
(3.37)
The MATLAB script implementing the above Newton-Raphson
load flow and the incorporation of the UPLC equations is given
in appendix A
CHAPTER FOUR
SIMULATION AND RESULTS ANALYSIS
This chapter presents the results obtained from the simulations
and analyzed in line with the stated objective of the project.
4.1 CASE 1: Newton-Raphson load flow carried out without the
UPFC, considered as the normal condition. This is result is
depicted in tables 4.1 and 4.2.
Table 4. 1:BUS VOLTAGES WITHOUT THE UPFC
bus voltage in pu voltage angle in degree
1.0600 0.0000
1.0000 -2.0612
0.9872 -4.6367
0.9841 -4.9570
0.9717 -5.7649
Figure 4. 1:voltages of the buses without the UPFC
between buses 3 and 4
Table 4. 2. LINE FLOWS AND LOSSES WITHOUT UPFC
4.2 CASE 2: Newton-Raphson load flow carried out with the
UPFC incorporated between buses 3 and 4 to control nodal
voltage and increase active power flows. This is result is
depicted in tables 4.3 and 4.4
Table 4. 3. BUS VOLTAGES WITH UPFC
bus voltage in pu voltage angle in degree
1.0600 0.0000
1.0000 -1.7693
1.0000 -6.0161
0.9917 -3.1906
0.9745 -4.9741
Figure 4. 2: voltages of the buses with the UPFC between
buses 3 and 4
Table 4. 4. LINE FLOWS AND LOSSES WITH UPFC
The power flows in the UPFC-upgraded network are different
from the original situation, as was to be expected. The two most
obvious differences are that bus 3 is receiving an additional 20%
and 53% more active power from generator buses 1 and 2,
respectively. The increase is a result of the UPFC series
converter's high active power requirements.
The robustness of the UPFC shunt bus will determine the
maximum amount of active power transferred between the
UPFC and the AC system, 3. The generator at bus 1 reduces its
reactive power generation by roughly 5.6% because the UPFC
generates its own reactive power, and the generator linked at bus
2 increases its reactive power absorption by roughly 22.6%.
Additionally, bus 3's nodal voltage magnitude is maintained at 1
p.u. by the UPFC shunt converter. It's important to remember
that the UPFC keeps the active and reactive powers at 40MW
and 2MVAR, respectively, when they leave the UPFC and head
towards bus 3.
Table 4.5: voltages of the buses with and without the UPFC
between buses 3 and 4
Bus
No
Bus
Code
Voltage
Magnitude
Angle Load
(MW)
Load
(MVAR)
Gen
(MW)
Gen
(MVAR)
Qmin Qmax
1 1 1.06 0 0.0 0.0 0.0 0.0 -500 500
2 2 1 0 20.0 10.0 40.0 0.0 -300 300
3 3 1 0 46.0 16.0 0.0 0.0 0 0
4 3 1 0 40.0 6.0 0.0 0.0 0 0
5 3 1 0 60.0 10.0 0.0 0.0 0 0
Table 4.6 Bus Data: IEEE 5 Bus System
From Bus To Bus R X B
1 2 0.02 0.06 0.06
1 3 0.08 0.24 0.05
2 3 0.06 0.18 0.04
2 4 0.06 0.18 0.04
2 5 0.04 0.12 0.03
3 4 0.01 0.03 0.02
3 5 0.08 0.24 0.05
Table 4.7 Line Data for IEEE 5 Bus
CHAPTER FIVE
CONCLUSION AND RECOMMENDATIONS
5.1 CONCLUSION
Both real powers expressed in watts, and reactive power,
expressed in volt-amperes reactive, or var, are produced and
consumed by components of AC systems. Useful task (like
driving motors and lighting lamps) is completed by real power.
The voltages that need to be regulated for system reliability are
supported by reactive power. Controlling reactive power
generation, absorption, and flow throughout the network
improves the voltage profile. System losses are avoided by
minimizing reactive power flows.
A power flow solution is a network solution under steady state
circumstances that is subject to specific limitations that govern
how the system functions. Given a set of power injections at
every bus and defined voltages, the power flow solution
provides the nodal voltages, phase angle, and power flows.
Reactive power generation, absorption, and network-wide flow
are all managed to provide voltage regulation. Reactive power
sources and sinks include rotating synchronous condensers,
shunt capacitors, shunt reactors, UPFCs, and other FACTS
devices. The UPFCs are adaptable devices that use power
electronic switching components to regulate nearly every
parameter that may be controlled in a power system.
This project concentrated on reactive power compensation and
the use of UPFCs to boost active power flows in transmission
lines. The power-flow problem has been solved using the
Newton-Raphson load flow method. A modified UPLC power
flow model was used to investigate the impact of UPFC on the
power system. The modified load flow program was utilized to
access the impact of UPFC on the system, and UPLC was
positioned between buses 3 and 4.
In MATLAB, the simulation was carried out. Plots were used to
depict the findings of a load flow analysis conducted on a five-
bus system, which revealed that the voltage profile of the system
had improved. Additionally, it was clear that the UPFC was
positioned at a bus where the voltage magnitude was kept at one
p.u.
Based on the data, it can be said that the UPFC has the greatest
influence on voltage compensation and that power flows to the
bus closest to it, with its impact decreasing with increasing
distance from the bus.
5.2 RECOMMENDATIONS
One research project's completion creates opportunities for work
in numerous other adjacent fields. Future work in the following
areas has been identified in the course of this research:
• A bigger interconnected power system, such as the IEEE 14
& IEEE 30 bus or the IEEE 118 bus, or even larger, can be
used for the load flow research.
• In addition to the UPFC, IPFC, STATCOM, and other
FACTS controllers can be included, and the impact on the
system can be examined. Fuzzy logic and genetic
algorithms can be used to determine the ideal position of
the UPFC.
• A comparison of the FACTS devices' economics to
alternative approaches can be done.
APPENDIX A
% THE PROGRAM WITHOUT UPFC
PowerFlowsData; %Function to read network data
[YR,YI] = YBus(tlsend,tlrec,tlresis,tlreac,tlsuscep,...
tlcond,shbus,shresis,shreac,ntl,nbb,nsh); %Function to calculate
the Ybus
% GENERAL SETTINGS
D = zeros(1,nmax);
flag = 0;
it = 1;
% CALCULATE NET POWERS
[PNET,QNET] =
NetPowers(nbb,ngn,nld,genbus,loadbus,PGEN,QGEN,...
PLOAD,QLOAD);
while ( it < itmax && flag==0 )
% CALCULATED POWERS
[PCAL,QCAL] = CalculatedPowers(nbb,VM,VA,YR,YI);
% CHECK FOR POSSIBLE GENERATOR’S REACTIVE
POWERS LIMITS VIOLATIONS
[QNET,bustype] =
GeneratorsLimits(ngn,genbus,bustype,QGEN,QMAX,...
QMIN,QCAL,QNET, QLOAD, it, VM, nld, loadbus);
% POWER MISMATCHES
[DPQ,DP,DQ,flag] =
PowerMismatches(nmax,nbb,tol,bustype,flag,PNET,...
QNET,PCAL,QCAL);
% JACOBIAN FORMATION
[JAC] =
NewtonRaphsonJacobian(nmax,nbb,bustype,PCAL,QCAL,VM,
VA,...
YR,YI);
% SOLVE FOR THE STATE VARIABLES VECTOR
D = JAC\DPQ';
% UPDATE STATE VARIABLES
[VA,VM] = StateVariablesUpdates(nbb,D,VA,VM);
it = it + 1;
end
[PQsend,PQrec,PQloss,PQbus] = PQflows(nbb,ngn,ntl,nld,...
genbus,loadbus,tlsend,tlrec,tlresis,tlreac,tlcond,tlsuscep,PLOAD
,...
QLOAD,VM,VA);
Psend=real(PQsend*100)';
Prec=real(PQrec*100)';
Ploss=real(PQloss*100)';
Qsend=imag(PQsend*100)';
Qrec=imag(PQrec*100)';
Qloss=imag(PQloss*100)';
PQbus=(PQbus*100)';
% End function Newton-Raphson
% Results
VA=VA*180/pi; %Nodal voltage phase angles (deg)
disp(['bus voltage in pu ','voltage angle in degree'])
SM = [VM;VA];
% - - - Main UPFC Program
PowerFlowsData; %Function to read network data
UPFCdata; %Function to read the UPFC data
[YR,YI] = YBus(tlsend,tlrec,tlresis,tlreac,tlsuscep,...
tlcond,shbus,shresis,shreac,ntl,nbb,nsh); %Function to calculate
the Ybus
% GENERAL SETTING
D = zeros(1,nmax);
flag = 0;
it = 1;
% CALCULATE NET POWERS
[PNET,QNET] =
NetPowers(nbb,ngn,nld,genbus,loadbus,PGEN,QGEN,...
PLOAD,QLOAD);
while ( it < itmax && flag==0 )
% CALCULATED POWERS
[PCAL,QCAL] = CalculatedPowers(nbb,VM,VA,YR,YI);
% CHECK FOR POSSIBLE GENERATOR’S REACTIVE
POWERS LIMITS VIOLATIONS
[QNET,bustype] =
GeneratorsLimits(ngn,genbus,bustype,QGEN,QMAX,...
QMIN,QCAL,QNET, QLOAD, it, VM, nld, loadbus);
% UPFC CALCULATED POWER
[PspQsend,PspQrec,PQcr,PQvr,PCAL,QCAL] =
UPFCCalpower...
(nbb,VA,
VM,NUPFC,UPFCsend,UPFCrec,Xcr,Xvr,Vcr,Tcr,Vvr,Tvr,PCA
L,...
QCAL);
% POWER MISMATCHES
[DPQ,DP,DQ,flag] =
PowerMismatches(nmax,nbb,tol,bustype,flag,PNET,...
QNET,PCAL,QCAL);
% UPFC POWER MISMATCHES
[DPQ,flag] =
UPFCPowerMismatches(flag,tol,nbb,DPQ,VM,VA,NUPFC,Flo
w,...
Psp,PSta,Qsp,QSta,PspQsend,PspQrec,PQcr,PQvr);
if flag == 1
break
end
% JACOBIAN FORMATION
[JAC] =
NewtonRaphsonJacobian(nmax,nbb,bustype,PCAL,QCAL,...
VM,VA,YR,YI);
% MODIFICATION OF THE JACOBIAN FOR UPFC
[JAC] = UPFCJacobian(nbb,JAC,VM,VA,NUPFC,UPFCsend,...
UPFCrec,Xcr,Xvr,Flow,PSta,QSta,Vcr,Tcr,Vvr,Tvr,VvrSta);
% SOLVE JOCOBIAN
D = JAC\DPQ';
% UPDATE THE STATE VARIABLES VALUES
[VA,VM] = StateVariablesUpdates(nbb,D,VA,VM);
% UPDATE THE TCSC VARIABLES
[VM,Vcr,Tcr,Vvr,Tvr] =
UPFCUpdating(nbb,VM,D,NUPFC,UPFCsend,PSta,...
QSta,Vcr,Tcr,Vvr,Tvr,VvrTar,VvrSta);
%CHECK VOLTAGE LIMITS IN THE CONVERTERS
[Vcr,Vvr] =
UPFCLimits(NUPFC,Vcr,VcrLo,VcrHi,Vvr,VvrLo,VvrHi);
it = it + 1;
end
%Function to calculate the power flows in the UPFC controller
[UPFC_PQsend,UPFC_PQrec,PQcr,PQvr] =
PQUPFCpower(nbb,...
VA,VM,
NUPFC,UPFCsend,UPFCrec,Xcr,Xvr,Vcr,Tcr,Vvr,Tvr);
[PQsend,PQrec,PQloss,PQbus] =
PQflows(nbb,ngn,ntl,nld,genbus,...
loadbus,tlsend,tlrec,tlresis,tlreac,tlcond,tlsuscep,PLOAD,QLOA
D,...
VM,VA);
Psend=real(PQsend*100)';
Prec=real(PQrec*100)';
Ploss=real(PQloss*100)';
Qsend=imag(PQsend*100)';
Qrec=imag(PQrec*100)';
Qloss=imag(PQloss*100)';
PQbus=(PQbus*100)';
% End of UPFC main program
%Print results
it; %Number of iterations
VA=VA*180/pi; %Nodal voltage phase angles (deg)
disp(['bus voltage in pu ','voltage angle in degree'])
SM = [VM;VA];
fprintf('%15.4f %23.4f\n',SM)
REFERENCES
S. Asha Kiranmai, M. Manjula and V.R.S. Sarma, “Mitigation of
Various Power Quality Problems Using Unified Series
Shunt Compensator in PSCAD/EMTDC,” 16th National
Power Systems Conference, 15th-17th Dec. 2010.
D. Mohanty, A, Ahamad, and M. A Khan, “Modeling,
Simulation and Performance Analysis of FACTS Controller
in Transmission line,” International Journal of Emerging
Technology and Advanced Engineering, Vol. 3, No. 5, pp.
429-435, May. 2013.
V. Mathad, F. R. Basanagouda, and S. H. Jangamshetti, “Voltage
Control and Power System Stability Enhancement using
UPFC,” International Conference on Renewable Energies
and Power Quality (ICREPQ’14) , Apr. 2014, Vol.1, No.12,
pp. 871-875.
S. S. Khonde, S. S. Dhamse, and A. G Thosar, “Power Quality
Enhancement of Standard IEEE 14 Bus System using
Unified Power Flow Controller,” International Journal of
Engineering Science and Innovative Technology (IJESIT),
Vol. 3, No. 5, pp. 323-334, Sept. 2014.
L. Gyugyi & Fellow, “DYNAMIC COMPENSATION OF AC
TRANSMISSION LINES BY SOLID-STATE
SYNCHRONOUS VOLTAGE SOURCES,” IEEE
Transactions on Power Delivery, Vol. 9, No. 2, pp. 904-
911, Apr. 1994.
L. Gyqyi, T. R. Rietman, A. Edris, C. D. Schauda, s. L .
Willirms, and , D.R. Torgerson, “THE UNIFIED
POWFBFLOW CONTROLLER: A NEW APPROACH TO
POWER TRANSMISSION CONTROL,” IEEE
Transactions on Power Delivery, Vol. 10, No. 2, pp. 1085-
1097, Apr. 1995.
Q. Yu, S. D. Round, L. E. Norum, and T. M. Undeland,
“Dynamic Control of a Unified Power Flow Controller,”
IEEE, pp. 508-514, 1996.
M. Noroozian, L, Angquist, M. Ghandhari and G. Anderson,
“USE OF UPFC FOR OPTIMAL POWER FLOW
CONTROL,” IEEE Transactions on Power Delivery, Vol.
12, No. 4, pp.1629-1634, Oct. 1997.
Z. Huang, Y. Ni, C. M. Shen, F. W. Felix, S. Chen and B. Zhang,
“ Application of Unified Power Flow Controller in
Interconnected Power Systems—Modeling, Interface,
Control Strategy, and Case Study,” IEEE Transactions on
Power systems, Vol. 15, No. 2, pp. 817- 824, May. 2000.
S. Muthukrishnan and A. Kumar, “Comparison of Simulation
and Experimental Results of UPFC used for Power Quality
Improvement,” International Journal of Computer and
Electrical Engineering, Vol. 2, No. 3, pp. 555-559, June.
2010.
S. Muthukrishnan and A. Kumar, “Enhancement of power
Quality in 14 Bus System Using UPFC,” Research journal
of Applied Sciences, Engineering and technology,” ISSN.
2040-7467, pp. 356-361, July. 2010.
D. Murali, M. Rajaram and N. Reka, “Comparison of FACTS
Devices for Power System Stability Enhancement,”
International Journal of Computer Applications, Vol.8,
No.4, pp.30-35, Oct. 2010.
A. R. Bhowmik and C. Nandi, “Implementation of Unified
Power Flow Controller (UPFC) for Power Quality
Improvement in IEEE 14-Bus System,” Arup Ratan
Bhowmik et al, Int. J. Comp. Tech. Appl., Vol. 2 (6),1889-
1896, 2011.
A. Rai, “Enhancement of Voltage Stability & reactive Power
Control of Distribution System Using Facts Devices,”
International Journal of Scientific Research Engineering &
Technology, Vol.1, No. 9, pp. 001-005, Dec. 2012.
M R. S. Reddy and M. V. Kumar, “Power Quality Improvement
in DFIG based Wind Energy Conversion System using
UPFC,” IOSR Journal of Engineering (IOSRJEN) Vol. 3,
No. 1, pp. 46-54, Jan. 2013.
K. Gaurav and N. Saxena, “Power Quality improvement using
UPFC,” International Journal of Electrical, Electronics and
Computer Engineering , Vol.2, No.2, pp. 30- 33, 2013.
S. Vaibhav Kale, R. P.Prashant and R. Khatri, “Unified Power
Flow Controller for Power Quality Improvement,”
International Journal of Emerging Science and Engineering
(IJESE), Vol.1, No. 10, pp. 1-4, Aug. 2013.
K. Ravichandrudu, P. S. Pramod Kumar, and, V.E. Sowjanya,
“MITIGATION OF HARMONICS AND POWER
QUALITY IMPROVEMENT FOR GRID CONNECTED
SYSTEM USING UPFC,” International Journal of
Application or Innovation in Engineering & Management
(IJAIEM), Vol. 2, No. 10, pp. 141-156 Oct. 2013.
B. Gopinath, N. Vinothini, and S. kumar, “Modeling of UPFC
Using Model Predictive Control and Bacterial Foraging
Algorithm,” International Journal of Innovative Research in
Computer and Communication Engineering, Vol. 2, No. 1,
pp. 2724-2731, Jan. 2014.
K. S. Lakshmi, G. Sravanthi, L. Ramadevi, and K. H. Chowdary,
“Power quality and stability improvement of HVDC
transmission System using UPFC for Different uncertainty
conditions,” International Journal of Scientific &
Engineering Research, Vol. 6, No. 2, pp. 795-801, Feb.
2015.
M. S. Soruban, J D. Sathyaraj, and J. J. Gnana Chandran,
“Power Quality Enhancement Using UPFC as an Active
Power Filter for Renewable Power Generation,”
International Journal of Advanced Research in Electrical,
Electronics and Instrumentation Engineering Vol. 4, No. 3,
pp. 1712-1718, March. 2015.
G. Srinivas and T. Santosh Chaitanya, “Enhancement of Power
Quality Using FACTS Devices (D-STATCOM),”
International Journal of Advanced Research in Electrical,
Electronics and Instrumentation Engineering, Vol. 4, No. 4,
pp. 1956-1965, Apr. 2015
P. Kundur Power System stability and control McGraw-
Hill, New York (2012)
Anderson, P. M., & Fouad, A. A. (2008). Power System Control
and Stability. Wiley-IEEE Press.
X. Jiang, J. H. Chow, A.-A. Edris, B. Fardanesh, and E.
Uzunovic, “Transfer path stability enhancement by voltage-
sourced converter-based FACTS controllers,” IEEE
Transactions on Power Delivery, vol. 25, pp. 1019-1025,
Apr. 2010.
L. G. c. E.-H. Narain G. Hingorani, consulting editor.,
Understanding FACTS : concepts and technology of
flexible AC transmission systems New York : IEEE Press
2000
P. Therond, P. Cholley, D. Daniel, E. Joncquel, L. Lafon, and C.
Poumarede, "FACTS research and development program at
EDF," in Flexible AC Transmission Systems (FACTS) -
The Key to Increased Utilisation of Power Systems, IEE
Colloquium on (Digest No.1994/005), 1994, pp. 6/1-615.
X.-P. Zhang, C. Rehtanz, and B. Pal, "FACTS-Devices and
Applications," in Flexible AC Transmission Systems:
Modelling and Control, ed: Springer, 2012, pp. 1-30
J. A. Suul, M. Molinas, and T. Undeland, "STATCOM-Based
Indirect Torque Control of Induction Machines During
Voltage Recovery After Grid Faults," Power Electronics,
IEEE Transactions on, vol. 25, pp. 1240-1250, 2010.
Thyristor-Controlled Series Capacitors for Power System
Compensation," IEEE Transactions on Power Delivery,
2004.
Sindekar, A & Parate, J. (2012). Reactive Power Control and
Transmission loss reduction with realization of SVC and
TCSC. (Electronic version). International Journal of
Engineering Science and Technology. 4 (7), 3592 – 3600
Singh, B. etal. (2010). Incorporation of FACTS Controllers in
Newton Raphson Load Flow for Power Flow Operation,
Control and Planning: A Comprehensive Survey.
(Electronic version). International Journal on Computer
Science and Engineering. 2 (6), 2117- 2124
Youtube Video: Design and Analysis of UPFC to Improve
Power Capacity: Technical University.
Youtube Video: Lecture on Analysis pf Unified Power
Controller: Technical University.
Enrique, A etal. (2004). FACTS Modelling and Simulation in
Power Networks. India: Thomson Press Ltd, New Delhi.
1